CO Detectors

The CMD5B5 series carbon monoxide detector uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 mA or voltage signal. The voltage signal may also be set to 0-5 or 0-10 V dc. The sensing range and output may be scaled to either 100, 150, 300, 400 or 500 ppm via the on-board menu. A front panel LCD is standard to ensure easy setup and operation. Other standard features include a back light for the LCD, a front panel test switch, status indication and an alarm buzzer. The test function may also be controlled remotely with a digital input signal. The on-board menu allows for local configuration of all device parameters. Optional features include one or two alarm relays and/or RS-485 network communications configured for either ModBus or BACnet® protocol.

Contact Us to Purchase
Features
  • Setup/calibration fully menu driven
  • Selectable ranges of 0-100, 150, 300, 400 or 500 ppm
  • Replaceable Electrochemical sensing element
  • Optional on board relays with field adjustable trip point.
  • Optional BACnet or Modbus communications
  • Powered by either an AC or DC source
  • Choice of three field adjustable analog output signals
  • Easy to calibrate in the field

For Replacement Sensor Modules

The CMD5B5 Series carbon monoxide detector uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 mA , 0-5 or 0-10 Vdc. The sensing range and output may be scaled to either 100, 150, 300, 400 or 500 ppm via the on-board menu. A front panel LCD is standard to ensure easy setup and operation. Other standard features include a back light for the LCD, a front panel test switch, status indication and an alarm buzzer. The test function may also be controlled remotely with a digital input signal. The on-board menu allows  local configuration of all device parameters.

Optional features include one or two alarm relays and/or RS-485 network communication configured for either ModBus or BACnet protocol.

Specifications

DESCRIPTION

ENGINEERING SPEC

SENSOR

CO Sensor, Electrochemical

AGENCY APPROVALS

Sensor is UL Recognized for ASNI/UL-2034 and UL-2075, E240671

SAMPLE METHOD

Diffusion

MEASUREMENT RANGE

0-100, 150, 300, 400, or 500 ppm (selectable)

ACCURACY

±5 ppm or ±5% of reading (whichever is greater)

0 to 50°C (32 to 122°F), 15 to 95 %RH

STABILITY

<5% signal loss/year

RESPONSE TIME

<35 seconds for 90% step change

LIFE EXPECTANCY

5-7 years in air

TYPICAL COVERAGE AREA

700m2 (7500ft2) or 15m (50ft) radius

POWER SUPPLY

24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectified)

CONSUMPTION

100 mA maximum with all options on

PROTECTION CIRCUITRY

Reverse voltage protected and output limited

OUTPUT SIGNAL

4-20 mA (Active), 0-5 or 0-10 Vdc (Selectable)

OUTPUT DRIVE AT CAPABILITY

Current: 450Ω maximum

Voltage: 10 KΩ minimum

OUTPUT RESOLUTION

10 bit PWM (±0.4ppm)

LCD DISPLAY

Displays PPM and menu parameters 1ppm, 35mm W x 15mm H (1.$” x 0.6”)

Alpha-numeric 2 line x 8 character with backlight

STATUS LED

2 color (red/green) on front panel

TEST SWITCH

Performs I/O tests, front panel and remote connection

BUZZER ALARM

85 db @ 10 cm

BUZZER TRIP POINT

Programmable 20-500 ppm in 10 ppm increments

BUZZER DELAY

Programmable 0-10 minutes in 1-minute increments

OPTIONAL RELAY OUTPUT

One or two Form C (N.O. and N.C.)

5 Amps @ 250 Vac, 5 Amps @ 30 Vdc, p.f. = 1

Relay 1 Trip Point: Programmable 20-500 ppm in 10 ppm increments

Relay 2 Trip Point: Programmable 20-500 ppm in 10 ppm increments

Relay Hysteresis: Programmable 10-100 ppm in 5 ppm increments

Relay Delay: Programmable 0-10 minutes in 1-minute increments

WIRING CONNECTIONS

Screw terminal block (14 to 22 AWG)

FIELD CALIBRATION

By applying calibration gas standard (contact Greystone for calibration kit)

COMMUNICATION

BACnet® or Modbus (Refer to installation instructions for full details)

OPERATING CONDITIONS

-20 to 50°C (-4 to 122°F), 0-90 %RH non-condensing

STORAGE TEMPERATURE

-20 to 60°C (-4 to 140°F)

ENCLOSURE

ABS, UL94-V, IP65 (NEMA 4X)

Space: 145mm W x 101mm H x 64mm D (5.7” x 4” 2.5”)

Duct: 145mm W x 101mm H x 240mm D (5.7” x 4” x 9.4”)

COUNTRY OF ORIGIN

Canada