Fixed Fire and Smoke Curtain

Creates a fire-resistant barrier.
Protects and separates a section of the building from fire or smoke damage in the event of a fire mishap.

  • Certified from itb poland as per en 12101-1:2005+a1:2006
  • Excellent mechanical properties, high cut resistance and flexibility
  • Anti-bacterial, anti-fungal and dew-resistant.
Contact Us to Purchase
Features
Fire Rating
Smoke Curtains 600°C for 120 minutes
Fire Curtains 1100°C for 120 minutes

Specifications

Technical information

Fabric

E-Glass filament fabric Width

100 - 150 cm ± 1 cm

39,37 - 59,06 inch

± 0,39 inch

Coating

Polyurethane + Filler Color Silver

Technical Data

Nominal values mettle Nominal values English

Test methods')

Weave of fabric

Twill 1/3 Twill 1/3 DIN 61 101 — 1/2

Weight of fabric

430 g/m2 ± 10 g/m2 12,68 oz/sy ± 0,29 oz/sy

DIN 53 854

Weight of coating side 1/2

20/20 g/m2 ± 5/5 g/m2 0,59/0,59 oz/sy ± 0,15/0,15 oz/sy DIN 53 854

Total weight

470 g/m2 ± 20 g/m2 13,86 oz/sy ± 0,59 oz/sy DIN 53 854

Total thickness

0,40 mm ± 0,05 mm coated 0,0157 inch ± 0,0020 inch coated

ISO 4603

Tensile strength wrap weft

> 6000 N/5 cm

> 4000 N/5 cm

> 682 lbs/inch

455 lbs/inch

DIN 53 857-1 >

Temperature range 2

-50°C / +200°C -58°F / +392°F

In-house test

Temperature range fabric 2

-60°C / +500°C -76°F / +932°F

Supplier data sheet

The temperature range in short term2I

-50°C / +600°C

-58°F / +1112°F In-house test

Tightness

Not applicable Not applicable